1910 Series Pressure Switch Our most popular series combines advanced design and precision construction to make these switches able to perform many of the tasks of larger, costlier units. Designed for air conditioning service, they also serve many fluidics, refrigeration, oven and dryer applications. For air and non combustible compatible gases, series 1900 switches have set points from 0.07 to 20 inches of water. Set point adjustment is easy with range screw located inside conduit enclosure. Internal location helps prevent tampering. 

Manual reset model 1900MR includes a special snap switch which latches on pressure increase above the setpoint. Switch must be manually reset after pressure drops below the setpoint.



Specifications

Temperature Limits: -30°F to 180°F
Maximum surge pressure: 10 psig
Rated pressure  45 inches of water
Pressure connections: 1/8" FNPT
Electrical rating: 15 amps, 120-480 volts, 60 Hz. A.C. resistive 
1/8 H.P. @ 125 volts; 1/4 H.P. @ 250 volts 
60 Hz. A.C. Dereate to 10 amps for operation 
at high cycle rates.
Wiring connections: 3 screw type; common, normally open and normally closed.
Set point adjustment: Screw type inside conduit enclosure
Housing: Aluminum die casting with chenical conversion coating 
for corrosion protection; zinc plated steel stamping
Diaphragm: Moulded Silicone rubber. Aluminum diaphragm plate
Calibration spring: Stainless steel
Weight: 1 lb.
Installation: Diaphragm vertical
Caution: For use only with air or compatible gases.


Ordering Information

Model Number
Set Point Range
inches of water
1910-00 0.07 to 0.15
1910-0 0.15 to 0.55
1910-1 0.40 to 1.75
1910-5 1.40 to 5.50
1910-10 3.0 to 11.75
1910-20 4.0 to 20.0
Manual Reset Models
1910-1-MR 0.40 to 1.75
1910-5-MR 1.40 to 5.50
1910-10-MR 3.0 to 11.8
1910-20-MR 4.0 to 20.0
Accessory
A329 Street "L" Adapter for 
applications requiring 
right angle connectors. 
Two required for differential 
pressures.