16L
Series Limit Control![]() |
The 16L series FM Approved Limit Controls for temperature
/ process applications set a new standard in 1/16 DIN power, flexibility
and value. Completly interchangable with the Dwyer 16A Series, the
16L Series offers a high level of features in a compact size.
Options for the 16L include Process Output Retransmission (Voltage or Current), RS-232 Serial Communication, or RS-485 Serial Communication.. Designed and built in the USA, the 16L family of controls offers the
highest levels of features, function, and quality available today.
|
| Selectable Inputs: | Thermocouple, RTD, DC Voltage, or DC Current selectable. |
| Input Impedance: | Thermocouple = 3 megohms minimum. RTD current = 200 µA.
Current = 10 ohms. Voltage = 5000 ohms. |
| Sensor Break Protection: | User determines control output to protect system after user set time. |
| Set Point Range: | Selectable |
| Display: | Two 4 digit, 7 segment 0.30" high LEDs. |
| Limit Action: | Reverse or Direct selectable. |
| On - Off Differential: | Adjustable 1° F, 1° C, or 1 count to full scale in 1° F, 1° C, or 1 count steps. |
| Accuracy: | ±0.25% of span, ±1 least significant digit. |
| Resolution: | 1 degree or 0.1 degree, selectable. |
| Line Voltage Stability: | ±0.05% over the supply voltage range. |
| Temperature Stability: | 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F) maximum (100 ppm / °C typical, 200 ppm / °C maximum). |
| Common Mode Rejection: | 140 db minimum at 60 Hz. |
| Normal Mode Rejection: | 65 db typical, 60 db at 60 Hz. |
| Isolation: | Relay and SSR outputs: 1500 VAC to all other inputs and outputs. |
| SP1 and SP2 Switched Voltage outputs: | 500 VAC to all other inputs and outputs, but not isolated from each other. |
| Process Output (Options 934, 936): | 500 VAC to all other inputs and outputs. |
| Supply Voltage: | 100 to 240 VAC, nominal., +10 -15%, 50 to 400 Hz. single phase; 132 to 240 VDC, nominal., +10-20%. |
| Power Consumption: | 5VA maximum. |
| Operating Temperature: | -10 to +55 °C (+14 to 131 °F). |
| Storage Temperature: | -40 to +80 °C (-40 to 176 °F). |
| Humidity Conditions: | 0 to 90% up to 40 °C non-condensing 10 to 50% at 55 °C non-condensing. |
| Memory Backup: | Nonvolatile memory. No batteries required. |
| Control Output Ratings: | SSR: 2.0 A @ 240 VAC at 25 °C (77°F). Derates to 1.0 A @ 55°
C (130°F).
Relay: SPST, Form A (Normally open), 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive; Pilot Duty Rating: 250VA, 2 A @ 120 VAC or 1 A @ 240 VAC. SPST, Form B (Normally closed), 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive; Pilot Duty Rating: 250 VA, 2 A @ 120 VAC or 1 A @ 240 VAC. |
| Switched Voltage (isolated): | 15 VDC @ 20 mA. |
| Panel Cutout: | 45 mm x 45 mm (1.775" x 1.775"). |
| Depth Behind Mounting Surface: | 115.3 mm (4.54"). |
| Weight: | 227 g (8 oz). |
| Agency Approvals: | Factory Mutual, CE, UL (when used as alarms only) |
| Front Panel Rating: | IP 66, (Type 4X). |
Options:
934 Analog Retransmission of Process Variable, 4 to 20 mADC. Output
may be scaled
to any place on the input scale to a minimum of 100 counts and a maximum
of 9999
counts.
936 Analog Retransmission of Process Variable, 0 to 10 VDC. Output
may be scaled
to any place on the input scale to a minimum of 100 counts and a maximum
of 9999
counts.
992 RS-485 Serial Communications. Allows remote computer to read and
write all
control parameters.
993 RS-232 Serial Communications. Allows remote computer to read and
write all
control parameters.
9502 Operation on 12/24 VAC/VDC power.
Phone: 604-254-9622
Fax: 604-254-3123
e-mail: info@johnsherman.com