John Sherman Agencies Ltd.
Contact Us!
Return to Controller Index
Return to Sherman Homepage

Dwyer Instruments Inc.16L Series Limit Control

16L Limit Control The 16L series FM Approved Limit Controls for temperature / process applications set a new standard in 1/16 DIN power, flexibility and value.  Completly interchangable with the Dwyer 16A Series, the 16L Series offers a high level of features in a compact size. 
 
  • Single or Dual Outputs 
  • Dedicated Reset Key 
  • Remote Reset Capability 
  • Isolated Outputs 
  • Dual or Single Display Programmable 
  • Peak / Valley Indication 
  • 4 Levels of Access Security 
  • Illuminated Keypad 
  • Fully Programmable Output Functions 
  • Factory Mutual and CE Approved 

  • The 16L offers universal input (10 thermocouple types, 4 RTD types, voltage, and current), single or dual set point, Peak / Valley indication, field configurable display, standard remote reset capability, and illuminated keys. 

    Options for the 16L include Process Output Retransmission (Voltage or Current), RS-232 Serial Communication, or RS-485 Serial Communication.. 

    Designed and built in the USA, the 16L family of controls offers the highest levels of features, function, and quality available today. 
     


    Specifications

    Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current selectable. 
    Input Impedance: Thermocouple = 3 megohms minimum. RTD current = 200 µA. 
    Current = 10 ohms. Voltage = 5000 ohms. 
    Sensor Break Protection: User determines control output to protect system after user set time.
    Set Point Range: Selectable
    Display: Two 4 digit, 7 segment 0.30" high LEDs.
    Limit Action: Reverse or Direct selectable.
    On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F, 1° C, or 1 count steps.
    Accuracy: ±0.25% of span, ±1 least significant digit.
    Resolution: 1 degree or 0.1 degree, selectable.
    Line Voltage Stability: ±0.05% over the supply voltage range.
    Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F) maximum (100 ppm / °C typical, 200 ppm / °C maximum). 
    Common Mode Rejection: 140 db minimum at 60 Hz.
    Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
    Isolation: Relay and SSR outputs: 1500 VAC to all other inputs and outputs.
    SP1 and SP2 Switched Voltage outputs: 500 VAC to all other inputs and outputs, but not isolated from each other.
    Process Output (Options 934, 936): 500 VAC to all other inputs and outputs.
    Supply Voltage: 100 to 240 VAC, nominal., +10 -15%, 50 to 400 Hz. single phase; 132 to 240 VDC, nominal., +10-20%. 
    Power Consumption: 5VA maximum.
    Operating Temperature: -10 to +55 °C (+14 to 131 °F).
    Storage Temperature: -40 to +80 °C (-40 to 176 °F).
    Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at 55 °C non-condensing.
    Memory Backup: Nonvolatile memory. No batteries required.
    Control Output Ratings: SSR: 2.0 A @ 240 VAC at 25 °C (77°F). Derates to 1.0 A @ 55° C (130°F).
    Relay: 
             SPST, Form A (Normally open), 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive; Pilot Duty Rating: 250VA, 2 A @ 120 VAC or 1 A @ 240 VAC. 
             SPST, Form B (Normally closed), 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive; Pilot Duty Rating: 250 VA, 2 A @ 120 VAC or 1 A @ 240 VAC.
    Switched Voltage (isolated): 15 VDC @ 20 mA.
    Panel Cutout: 45 mm x 45 mm (1.775" x 1.775").
    Depth Behind Mounting Surface: 115.3 mm (4.54").
    Weight: 227 g (8 oz).
    Agency Approvals: Factory Mutual, CE, UL (when used as alarms only) 
    Front Panel Rating: IP 66, (Type 4X).

    Ordering Information:

    To order, specify part number by filling the boxes with the appropriate numbers. If no options are desired, leave those boxes
    blank:   

    Options:

    934 Analog Retransmission of Process Variable, 4 to 20 mADC.  Output may be scaled
    to any place on the input scale to a minimum of 100 counts and a maximum of 9999
    counts.

    936 Analog Retransmission of Process Variable, 0 to 10 VDC.  Output may be scaled
    to any place on the input scale to a minimum of 100 counts and a maximum of 9999
    counts.

    992 RS-485 Serial Communications. Allows remote computer to read and write all
    control parameters.

    993 RS-232 Serial Communications. Allows remote computer to read and write all
    control parameters.

    9502 Operation on 12/24 VAC/VDC power.


    Contact Us!

    John Sherman Agencies Ltd.
    1641 Venables Street
    Vancouver, British Columbia, Canada
    V5L 2H1

    Phone: 604-254-9622
    Fax: 604-254-3123

    e-mail: info@johnsherman.com